
ZQSCB-3300/35
This product is primarily used in urban rail transit, where its rectifier unit provides traction DC power for subways. The product capacity ranges from 2000kVA to 4000kVA. The primary windings of its two rectifier transformers have phase angles of +7.5° and -7.5° respectively. When both transformers operate simultaneously, they form a 24-pulse rectification circuit. The 12-phase 24-pulse dry-type traction rectifier transformer meets all performance indicators required for subway power supply, and it is particularly effective in mitigating the impact of higher-order harmonics from the rectification device on the power grid.
| Parameter name | Unit | Parameter value |
| Product Model | – | ZQSCB-3300/35 |
| Rated capacity | KVA | 3300 |
| Rated voltage ratio | KV | 35/1.18/1.18 |
| short-circuit impedance | % | 8 |
| rated frequency | Hz | 50 |
| Connection group label | – | Dy5d0/Dy7d2 |
| Insulation level | KV | LI170AC70/AC10 |
| cooling method | – | AN |
| No-load loss | KW | S4.67 |
| load loss | KW | s22.94 |
| Temperature Rise Limit | K | <85 |
| Noise (sound pressure level) | dB(A) | ≤60 |
*Respeitamos a sua confidencialidade e todas as informações são protegidas.
Sou o Leo, o chefe da equipa de vendas da Huaxiang. Eu e a minha equipa teremos todo o prazer em conhecê-lo e saber tudo sobre o seu negócio, requisitos e expectativas.
*Respeitamos a sua confidencialidade e todas as informações são protegidas.
Sou o Leo, o chefe da equipa de vendas da Huaxiang. Eu e a minha equipa teremos todo o prazer em conhecê-lo e saber tudo sobre o seu negócio, requisitos e expectativas.